AREX+ 110 horizontal is a mechanical ventilation unit with dual airflow and heat recovery, designed for ceiling installation. The unit, with excellent performance, is designed to supply the required airflow for air renewal and to recover heat from the exhaust air, transferring it to the incoming air. The units, with high performance, are constructed with a robust sheet metal structure.
Each unit is equipped with:
All units, compliant with European ERP directives and EN standards, are CE and DoP marked.
The units are designed for the following functions in residential or small commercial buildings:
They can be installed in a false ceiling and can be ducted through both rigid and flexible ventilation ducts.
The air renewal capacity of each unit is 110 m³/h.
AREX+ 110 horizontal ensures an air renewal rate of 0.5 Volumes/h for rooms with a floor area of 120 m² (assuming a height of 2.80 m).
The unit is equipped with a centrifugal fan with reverse blades and a maintenance-free motor (1), with overload thermal protection, which extracts stale air and expels it outside. A second fan (2), with the same characteristics, draws fresh air from the outside and sends it into the rooms. Through two heat exchangers, arranged in series (3), the heat contained in the exhaust air is recovered and transferred to the fresh air. The crossflow heat exchangers are made of aluminum. The external air is filtered (4), as is the stale air extracted from the technical rooms (5). When the external air temperature drops to the point where there is a risk of ice forming in the heat exchangers, a safety thermostat (6) stops the fan for a sufficient time. A control unit (7) ensures the proper operation of the machine. The condensation formed in the heat exchangers is collected in the tray (8) and drained through the drain tube (9).
The airflow rate can be adjusted manually or automatically according to the needs. Automatic adjustment is possible with the installation of sensors capable of detecting odors and pollutants (optional).
Description | Heat Recovery Unit AREX+ 110 horizontal |
|
Code | VRHS11 | |
Airflow rate | m³/h | 110 |
Max static pressure | Pa | 100 |
Efficiency | % | > 90% |
Thermal power recovered in winter | W | 1285 |
Thermal power recovered in summer | W | 439 |
Power consumption | W | 60 |
Current consumption at max speed | A | 0,8 |
Power supply | V/ph/Hz | 230/1+N/50 |
Empty weight | kg | 25 |
Noise level at max speed | dB(A) | 52 |
Note:
The exchange efficiency and the power recovered in winter are based on an ambient air temperature of +20°C at 50% RH and external air temperature of -5°C at 80% RH.
The thermal power recovered in summer is based on an ambient air temperature of +26°C at 50% RH and external air temperature of 35°C at 70% RH.
Under different working conditions, the values obtained will differ the further one moves from nominal conditions.
Ceiling-mountable air handling unit in galvanized sheet metal, with air renewal function and heat recovery from the exhaust air for maximum energy efficiency. Air renewal rate of 110 m³/h, counterflow heat exchanger efficiency over 90%, sound power level 52 dB(A) according to UNI EN ISO 3746:1997. Built-in automatic free cooling and dirty filter signal according to ErP 2018
For ceiling installation (in a false ceiling), it is recommended to use appropriately sized brackets and fixings, which should be connected to anti-vibration joints selected according to the type of structure to which they will be fixed. It is recommended to line the inside of the false ceiling with high-density sound-absorbing material and provide one or more openings for extracting the machine and subsequent cleaning of the air filters, checking the refrigeration circuit, maintenance, and checking the electrical panel. Provide an opening in the false ceiling large enough to completely disassemble and extract the unit.