Falko OC is the Fancoil for suspended ceiling installation. Thanks to the height of only 24 cm and the high efficiency exchange battery, it can be installed inside the suspended ceilings in the residential setting. The downward air intake is changeable at site into intake from behind. The condensate collection tray has DN 20 connection. The motor has three live inputs for speed selection. The frame is made of galvanized metal sheet. The air filter is removable, on the intake. Water connections, 3/4” F placed on the left side.
All units, compliant with European directives, are provided with CE (TUV) marking and relative certificate of conformity.
All measurements are in mm:
CODE | DESCRIPTION | A [mm] | B [mm] |
---|---|---|---|
TCM05A | FALKO 510 OC | 687 | 894 |
TCM08A | FALKO 850 OC | 832 | 1039 |
TCM14A | FALKO 1360 OC | 1112 | 1319 |
Technical data
FALKO OC 510 TCM05A |
FALKO OC 850 TCM08A |
FALKO OC 1360 TCM14A | ||||||||
---|---|---|---|---|---|---|---|---|---|---|
Description | ||||||||||
Code | ||||||||||
H |
M |
L |
H |
M |
L |
H |
M |
L |
||
Total cooling power 7°C (1) |
kW |
2.79 |
2.38 |
1.82 |
4.46 |
3.80 |
2.91 |
7.25 |
6.17 |
4.72 |
Sensible cooling power |
kW |
2.02 |
1.72 |
1.32 |
3.22 |
2.74 |
21.0 |
5.25 |
4.47 |
3.42 |
Water flow rate |
l / min |
8.0 |
6.8 |
5.2 |
12.0 |
10.2 |
7.8 |
20.0 |
17.0 |
13.0 |
Pressure drop FALKO OC only |
kPa |
36 |
26 |
16 |
32 |
24 |
14 |
46 |
33 |
19 |
Pressure drop kit 2 or 3 ways kvs=4 |
kPa |
1.4 |
1.0 |
0.6 |
3.2 |
2.3 |
1.3 |
9.1 |
6.4 |
3.7 |
Heating power 45 °C (2) |
kW |
3.36 |
2.87 |
2.19 |
5.38 |
4.58 |
3.50 |
8.73 |
7.43 |
5.68 |
Water flow rate |
l / min |
10 |
8.2 |
6.3 |
15.0 |
12.3 |
9.4 |
25.0 |
20.5 |
15.7 |
Pressure drop FALKO OC only |
kPa |
58 |
38 |
26 |
51 |
34 |
20 |
72 |
48 |
28 |
Pressure drop kit 2 or 3 ways kvs=4 |
kPa |
2.2 |
1.5 |
1.0 |
5.0 |
3.4 |
2.0 |
14 |
9.2 |
5.4 |
Rated air flow |
mc / h |
510 |
382 |
255 |
850 |
640 |
425 |
1360 |
1020 |
680 |
Air Nominal Head |
Pa |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
30 |
Sound pressure (*) |
dB (A) |
42 |
<42 |
<42 |
46 |
<46 |
<46 |
48 |
<48 |
<48 |
Power supply-protection grade. |
V / ph/ Hz |
230/1 + N/50----IP23 |
||||||||
Electrical consumption |
W |
59 |
41 |
27 |
87 |
65 |
44 |
156 |
118 |
81 |
Maximum current |
A |
0.33 |
0.23 |
0.15 |
0.38 |
0.37 |
0.25 |
0.89 |
0.67 |
0.47 |
Hydraulic Connections |
inch |
¾ F” (DN 20) |
||||||||
Water content |
Liters |
|||||||||
Condensate drainage pipe |
mm |
DN 20 |
||||||||
Maximum operating pressure |
MPa |
1.6 |
||||||||
Net Weight |
Kg |
16.4 |
18.9 |
26 |
Cod. TCM05A — Fancoil Falko Ceiling 510 OC Standard
Hydronic terminal for ceiling mounting, composed of high efficiency copper-aluminum exchange battery with spindle finned package, frame internally covered with sound absorbent material. With quiet fan assembly. Three-speed control by live inputs. Complete with condensate collection tray and thin weft synthetic removable filter. Nominal air flow rate 510 m3/h, thermal power in cooling 2'788 W, heating 3'360 W. Height: 240 mm. Hydraulic connections 3/4” M.
Cod. TCM08A — Fancoil Falko Ceiling 850 OC Standard
Cod. TCM14A — Fancoil Falko Ceiling 1360 OC Standard
Hydronic terminal for ceiling mounting, composed of high efficiency copper-aluminum exchange battery with spindle finned package, frame internally covered with sound absorbent material. With quiet fan assembly. Three-speed control by live inputs. Complete with condensate collection tray and thin weft synthetic removable filter. Nominal air flow rate 1'360 m3/h, thermal power in cooling 7'248 W, heating 8'734 W. Height: 240 mm. Hydraulic couplings 3/4” M.
Fan head curves:
Pressure drop Falko OC only
Pressure drop OC with 2 or 3 w kit