Newsletter Subscription
Enter your email and we will send you more information
The thermostat with humidity control is a robust electronic device that allows you to set and control optimal temperature and humidity conditions, both in summer and winter, without condensation.
The thermostat has integrated room temperature and humidity probes, as well as an additional external probe, connectable to measure the temperature of the radiant surface (floor or ceiling). The external probe is supplied in the package). The chronothermostat is equipped with a backlit LCD panel for quick viewing and setting of the desired temperature and humidity values. TH+ has two phase outputs, one to power the activation of heating/cooling, the other to turn on the dehumidifier. TH+ has algorithms both to continuously calculate the dew point and prevent possible condensation phenomena, and to regulate temperature and humidity according to the highly precise proportional integral (PI) method.
The thermostat with integrated humidity control is used in cooling applications, underfloor and ceiling, where you want to perform precise and reliable control of temperature and humidity conditions, with constant control of the dew point. The thermostat with integrated humidity control combines the functions of temperature, humidity and dew point control in a single instrument. TH+ has internal probes necessary to perform temperature and humidity control both to give consent to heating/cooling and to start the dehumidifier and maintain the desired humidity. Through a probe, to be installed inside the ceiling or floor, TH+ is able to maintain the temperature of the radiant surface above the dew point. TH+ is therefore the ideal instrument for cooling/heating systems with centralized mixing, when you want to control the humidity and temperature conditions of the individual thermal zones, as well as continuously prevent the temperature of the radiant panels from being below the dew point. Unlike control systems based only on the flow temperature, TH+ measures the actual temperature of the radiant surface and continuously compares it with the dew point temperature. This comparison is very precise and allows the water flow to be blocked only in the presence of critical conditions and, conversely, to power the panels at maximum power when there is no risk of condensation.
Thanks to the integrated probes, the thermostat continuously monitors the dew point based on the humidity and temperature conditions of the environment, and compares it with the surface temperature of the radiant surface. When conditions favorable to the formation of condensation are detected, TH Integra closes the heads and activates the dehumidifier to re-establish safe conditions. Once optimal conditions have been restored, it allows the heads to be opened to resume cooling until the set temperature is reached. In safe conditions, the thermostat detects the room temperature and compares it with the desired temperature (setpoint), in case of deviation it activates heating or, in summer mode, cooling. The larger the difference between the two values, the longer the heating/cooling shutdown time. As the ambient temperature approaches the desired one, the cycles become shorter, until the ideal equilibrium, which converges to a constant value. TH Integra also detects the relative humidity and, if the desired value is exceeded, activates the dehumidifier (only in summer operation).
U.M. | Termoumidostato WiFi | ||
Cod. SQCT14 | |||
Dimensioni | Mm | 86 x 62 | |
Assorbimento | W | <1 | |
Corrente nominale | A | 0,007 | |
alimentazione | - | 230 V +- 10% AC monfase 50 Hz | |
Portata Nominale relè | A |
|
|
Programmi impostabili | n° | 2 x i gg feriali, 2 x sabato e domenica | |
Classe di protezione elettrica | IP | IP20 | |
Termperatura di funzionamento | °C | 0-45°C, 5-95%RH (senza condensa) | |
Precisione di misura | °C | + - 5 % | |
Setpoint | °C | 5 - 35 °C | |
Display | LCD | ||
Installazione | scatola dedicata | ||
Peso | g | 15 |
Automatic room temperature and humidity control device for radiant heating and cooling systems, with PI regulation algorithm for continuous control of the dew point with the possibility of input from NTC probe for comparison with the radiant surface temperature and automatic exclusion of the thermal zone in the event of possible condensation formation. Two outputs in phase for heating/cooling consent and dehumidifier consent.